Product description of FM200
forede Cabinet type heptafluoropropane fire extinguishing device is also called pipeless fire extinguishing device and prefabricated fire extinguishing device. It consists of fire extinguishing agent bottle group, container valve, electromagnetic drive device, metal hose, signal feedback device, nozzle, cabinet, etc.


Product Specification of FM200
SYSTEM DATA | |||||
Model | GQQ40/2.5- JM | GQQ70/2.5- JM | GQQ90/2.5- JM | GQQ120/2.5- JM | GQQ150/2.5- JM |
Cylinder Capacity (L) | 40 | 70 | 90 | 120 | 150 |
| Cabinet Size(mm) | 500×481× 1450 | 500x481x1450 | 500x481x1600 | 500x481x1900 | 500x531x1900 |
| Max. Working Pressure (MPa) | 4.2 | ||||
Storage Pressure (MPa) | 2.5 | ||||
Working Temperature Range | 0~50°C (System room) | ||||
Operating Voltage (V) | AC 220 | ||||
Back-Up Power (V) | DC 24 | ||||
Discharging Time (S) | ≤10 | ||||
System Startup Method | Automatic / Manual Operation | ||||
FAQ
Q1:How long does it take to produce the product?
Conventional products and small quantities can be produced within 20 days. The specific production time needs to have specific products and product quantities to confirm.
Q2:Is the sample provided for free?
A few small products like sprinkler decorative covers can be provided for free, but the buyer needs to pay for the shipping. Other products need to be confirmed according to the specific situation.
Q3:What is the production time of the sample?
A sample will be produced within 20 days
Hot Tags: 40l single cabinet fm200 gas system for fire fighting, China, manufacturers, suppliers, wholesale, price, Cabinet FM 200 Fire Protection System, Cabinet FM 200 Fire Suppression System, Portable Ground Monitor, Cabinet FM 200 Fire Protection
-Low concentration of HFC
-227ea required means less visual obscurity and minimal risk to personnel.
-Small quantity of agent discharged minimises over pressurisation of the protection area.
-Max Safety for personnel due to low toxicity.
-High effective with 10 second discharge time when used with automatic detection.
-Prevent re-ignition as long as concentration levels are maintained.
-Two kinds of working pressure system are available,(25 bar / 360 psi and 42 bar / 600 psi).