Product Introduction:
Overview Model WAV-1 Alarm Check Valve is a wet pipe sprinkler system water supply check valve that makes possible the installation of sprinkler systems in buildings not subject to freezing temperatures. It is designed so that water pressure in the piping system will hold back water pressure at...
Send Inquiry
Description
Technical Parameters
Products Description

 

1

Alarm Check Valve

 

Model WAV-1 Alarm Check Valve Alarm check valve is mainly used in wet pipe fire protection system, which prevents the reverse flow and controls water pressure. It automatically actuates alarm when water flows into the system upon fire sprinkler operation. 

 

The Alarm Check Valve serves as a check valve by trapping pressurized water above the clapper and preventing reverse flow from sprinkler piping.
 
The valve is trimmed with a water bypass line. The bypass line allows pressure surges to enter the system and to be trapped above the alarm check valve's clapper without the clapper lifting and causing false alarms.
 
Alarm check valve is mainly used in wet pipe fire protection system, which prevents the reverse flow and controls water pressure. It automatically actuates alarm when water flows into the system upon fire sprinkler operation.

 

Products Parameters

 

Size
4" (DN100)
6" (DN150)
Inlet Connection Style
Flange
Flange
Outlet Connection Style
Flange Flange
Shipping Weight
55lbs∕25kg
75lbs∕34kg
Max. Working Pressure
175 psig∕1.2 MPa (12 bar)
Factory Hydro Test
100% @ 350 psig∕2.4 MPa (24 bar)
Standard Finish
Red Painted
Flange Specification
Flange: Class 150 ANSI B16.1
Required Accessories
Standard Trim
Optional Accessories
Retard Chamber, Water Motor Alarm, Alarm Pressure Switch
Installation Manner
Vertically
Listings and Approvals
FM APPROVAL

 

Instructions

 

The trim sets for the Model WAV-1 Alarm Valve are arranged for rapid, easy and compact attachment, and serves as connection points to Alarm and other devices. The trim also serves as means for testing the operation of the alarm devices without causing the system to operate.

 

1. Constant Pressure Closed Drain

This trim set is used where water supply pressure does not vary, such as tank supplies. An automatic draining is provided to drain the mechanical sprinkler alarm line. This drain connection should be piped separately from the 2" (50mm) main drain.

 

2. Variable Pressure With Open Retard Chamber Drain

Retard Chamber is required. This trim set is used where water supply pressures vary, such as encountered with city water supplies. An open drip cup should be provided to drain the retard chamber and the mechanical sprinkler alarm line. This drain connection should be piped separately from the 2" main drain.
 
FAQ

 

Q:Is the sample provided for free?

A:A few small products like sprinklers decorative covers can be provided for free, but buyers pay for freight. Other products need to be confirmed.

 

Q:What is the production time of the sample?

A:Generally speaking, it isn't a large-scale purchase, and the lead time about 15 working days. Of course, having an urgent order, please reconfirm with us.

 

Q:How to mail the samples?

A:Small samples are usually sent by express (DHL, UPS, FEDEX, TNT). If the buyer has other opinions, both parties can discuss with each other.

 

Q:How long does it take to produce the product?

A: Conventional products and small quantities can be produced within 15 days. The specific production time needs to have specific products and product quantities to confirm.

 

 

Hot Tags: alarm check valve in fire fighting system, China, manufacturers, suppliers, wholesale, price, Elevated Fire Water Monitor, BS Angle Landing Valve, BS Hydrant Valve, Remote Water Foam Monitor, Breeching Inlet, Fire Deluge Valve

Send Inquiry
Quanzhou Forede Firefighting Equipment Co.,Ltd
contact us