1. The number of indoor fire monitors should not be less than two, and the height of the fire monitors should ensure that the fire jets are not affected by the upper building components, and the water jets of the two water guns can reach the protected area at the same time. A part.

The indoor system should adopt a wet water supply system, and fire fire pump start buttons should be set at the fire cannon location.

When a fire monitor platform is set up, its structural strength should be able to meet the requirements of fire gun ejection reaction, and its structural design should be able to meet the requirements of normal use of fire monitors.

2. The arrangement of outdoor fire monitors should be such that the jets of fire monitors can completely cover the protected place and the protected objects, and should meet the requirements of fire suppression intensity and cooling intensity.

1.Fire cannons should be set in the upwind direction that prevails in the protected place.

2. A fire turret should be installed when the fire extinguishing object is high in height and area, or when the jet of the fire monitor is blocked by a large obstacle.

3. Fire guns should be arranged outside the dykes of Class A, B, and C liquid storage tanks. When the requirements of Article 2 cannot be met, they can be arranged inside the dykes. At this time, effective explosion protection should be adopted for remotely controlled fire guns and fire turrets. And thermal protection measures.

4. The number of fire monitors for liquefied petroleum gas and natural gas loading and unloading terminals and Class A, B, and C liquid and oil loading and unloading terminals shall not be less than two. The range of foam guns shall meet the range of oil and gas tanks covering the design ship type. The range of the gun should meet the entire ship range covering the design ship type.