Extended coverage sprinkler head refers to a sprinkler head with a specific protection area larger than a conventional sprinkler head, referred to as an EC sprinkler head (abbreviation for extended coverage). It has basically the same structure as a sprinkler head, and the main difference lies in the shape of the splash plate EC nozzles are generally used in light-risk and medium-risk places, and their maximum coverage is about 5m×7m. The protection area of the nozzle is 37.2m2, while the maximum protection area of the standard nozzle is only 20m2. It can be seen that the correct selection and use of EC Nozzles can effectively reduce system cost.
Extended Coverage Sprinkler Applicable Locations:
1. Wet systems should be used in places where the ambient temperature is not lower than 4°C and not higher than 70°C.
2. Dry systems should be used in places where the ambient temperature is lower than 4°C or higher than 70°C.
3. Places with one of the following requirements shall adopt the pre-action system:
1. When the system is in quasi-working state, it is strictly forbidden to leak water from the pipeline;
2. It is strictly forbidden to spray the system by mistake;
3. Replace the dry system.
4. In places where water spraying must be stopped in time after fire extinguishing, a pre-action system with repeated opening and closing shall be adopted.
5. The deluge system should be used in places with one of the following conditions: 1. The horizontal spread of the fire is fast, and the opening of the closed nozzle cannot make the spray water effectively cover the fire area in time; 2. The indoor headroom height exceeds Article 6.1.1 of this code stipulations, and the initial fire must be quickly extinguished; 3 serious danger level Ⅱ.
6. For warehouses that meet the conditions specified in 5.0.6 of this code, when installing an automatic sprinkler system, it is advisable to use quick-response early suppression sprinklers and a wet system.
7. In places where there are many flammable liquids, it is advisable to adopt an automatic water spray-foam combined system in one of the following ways: 1 Use foam fire extinguishing agent to strengthen the performance of the closed system; Foam strengthens the fire extinguishing efficiency; 3. Spray foam to extinguish the fire in the early stage of the deluge system, and spray water to cool down in the later stage to prevent re-ignition;