1. In addition to the ceiling type sprinklers and the sprinklers installed under the ceiling, the distance between the splash plate and the top plate of the vertical type and pendant type standard sprinklers should not be less than 75mm and should not be greater than 150mm.
2. When sprinklers are arranged on the plane below the bottom surface of beams or other obstacles, the distance between the splash plate and the top plate should not be greater than 300mm, and the vertical distance between the splash plate and the bottom surface of beams and other obstacles should not be less than 25mm. Greater than 100mm.
3. When arranging nozzles between beams, it shall comply with the provisions of Article 7.2.1 of this code. When it is really difficult, the distance between the splash plate and the top plate should not be greater than 550mm.
4. For the sprinklers arranged between the beams, when the distance between the splash plate of the sprinklers and the roof reaches 550mm, but still fails to meet the requirements of Article 7.2.1, additional nozzles should be installed under the bottom of the beams.
5. The vertical distance between the sprinkler under the ribbed beam plate and the splash plate and the bottom surface of the densely ribbed beam plate shall not be less than 25mm and shall not be greater than 100mm.
6. In places where the clearance height does not exceed 8m, for cross beams arranged at a distance of no more than 4×4 (m), one sprinkler head can be arrangbetween the beameds, but the water spraying intensity should still meet the requirements in Table 5.0.1.